Klemsan
606011 RAPIDUS 211R
Power Factor Controller (1Ø-12 steps)

  • TECHNICAL INFO
  • CERTIFICATES
  • DOWNLOADS
  • ORDER INFO
  • CREATE PDF
General Measuring system
  LCD Screen
  Language Support Turkish, English, Russian
  Battery
  Real Time Clock
  Password Protection
  Current Transformer Ratio 1 - 5000
  Voltage Transformer Ratio 1 - 5000
  Demand Period 1-60 min. adjustable
  Connection Type Single phase (L-L or L-N) voltage connection with 1 CT
  Measurement in Quadrants 4
  Number of Measurements in a Period 512
  LCD/Display Refresh Period 1 sec.
  Networks TT, TN, IT
  Phasor Diagram Available
  Min./Max./Demand Values
 
 
Control Operations and Functions Compensation Modes Rapidus (Intelligent control mode)
    Sequential
    Linear
    Circular
    Manual
  Step Configurations Manually Assigned
    Predefined 1-1-1-1, 1-1-2-2, 1-2-2-4, 1-2-3-3, 1-2-4-4, 1-1-2-4, 1-2-3-4, 1-2-4-8, 1-1-2-3
    DCM
    Fixed Step Assigment
    Power (kVAr) 0.00-1000 adjustable
    Type 3Ø capacitor, 3Ø shunt reactor adjustable
  Power Factor Settings Target 1 cosØ 0.8 cap. to 0.8 ind. adjustable
    Target 2 cosØ 0.8 cap. to 0.8 ind. adjustable
Control Operations and Functions Learning Step Powers and Connections
  Dual cosØ Target
  4 Quadrant operation for generators
  Time Delays Step Activation Time 1-600 sec. adjustable
    Step Deactivation Time 1-600 sec. adjustable
    Step Discharge Time 3-1000 sec. adjustable
Control Operations and Functions Phase Shift Angle ±45 degree adjustable
  Averaging Time Off, 5 sec, 10 sec, 20 sec, 30 sec, 40 sec, 50 sec, 60 sec adjustable
Energy Measurement Number of Tariffs 1
  3Ø Phase Energy Meters Available
Current Measurement Input Measurement Range 10mA-6A AC
  Overvoltage Category 300 V Cat II
  Measurement Surge Voltage 2 kV
  Power Consumption <0.2 VA
  Intermittent Overload 100A for 1 sec.
  Sampling Frequency between 45-65 Hz 25.6 kHz
Voltage Measurement Input Overvoltage Category 300 V Cat III
  Measured Range L-N 95-410VAC ±10%
  Measured Range L-L 95-410VAC ±10%
  Measured Frequency Range 45-65 Hz
  Power Consumption <0.1 VA
  Sampling Frequency between 45-65 Hz 25.6 kHz
Power Quality Measurements Harmonics for Current and Voltage Phases Up to 51st
  THD - Voltage in %
  THD - Current in %
Measurement Accuracy According to IEC 61557-12 Total Active Power Class 0.2
    Total Reactive Power Class 1
    Total Apparent Power Class 0.2
    Total Active Energy Class 0.5
    Total Reactive Energy Class 2
    Frequency Class 0.05
    Current Class 0.2
    Neutral Current Class 0.5
    Voltage Class 0.2
    Power Factor Class 0.5
    THDV, THDI Class 1
  According to IEC 62053-22 Total Active Energy Class 0.2S
  According to IEC 62053-23 Total Reactive Energy Class 2
Input and Outputs Compensation Relay Outputs Number of outputs 12
    Type NO (SPST)
    Max. Switching Current 2A
    Max. Switching Voltage 250VAC
    Max. Switching Power 1250VA
    Mechanical Lifetime ≥ 10.0000000 operations
    Electrical Lifetime Operations (for NO side) 5×104(5A@250VAC) 1×105(5A@30VDC)
  Alarm Relay Outputs Number of outputs 2
    Type NO (SPST)
    Max. Switching Current 4A
    Max. Switching Voltage 250VAC
    Max. Switching Power 1250VA
    Mechanical life time ≥ 10.0000000 operations
    Electrical life time operations (for NO side) 5×104(5A@250VAC) 1×105(5A@30VDC)
  Generator/ Day-Night Input Number of Inputs 1
    Frequency 45-65Hz
    Input Present or Not 95-240VAC
Input and Outputs Digital Outputs ---
  Analog Outputs ---
Supply Auxilary Supply Input ---
  Voltage La-Lb'den ±10% 95-410VAC
  Frequency 45-65Hz
Supply Consumption AC < 10VA
    DC ---
Data Logging with timestamp Min./Max./Avg. Values Hourly Records 1920 Hours x 68 Different Paramaters
    Daily Records 240 Days x 68 Different Paramaters
    Monthly Records 36 Months x 68 Different Paramaters
Data Logging with timestamp Demand 4 Months x 16 Different Parameters
  Alarm records 50
Communication Protocol Modbus RTU
  Baud rate 2400-115200 bps adjustable
  Parity number ---
  Stop bit 1
  Address 1-247
  Isolation 2000V RMS
Mechanical Properties Weight (g) 663g
  Protection Class Front IP40 / Rear IP20
  Mounting Type Panel Mount
  Packing Unit 1
Cable Cross Sections Voltage, Current, All Relay Outputs, Gen Input Stranded: 2.5mm² - 14AWG
    Solid: 4mm² - 12AWG, 2x1.5mm² - 2x16AWG
  RS 485 Stranded: 1.5mm² - 16AWG
    Solid: 1.5mm² - 16AWG, 2x0.75mm² - 2x18AWG
Ambient Conditions Operating Temperature -20°C +55°C
  Storing Temperature -30°C +80°C
  Relative Humidity (no condensation) Maks. 95%
EMC-EMI EN 61000-6-1:2011
  EN 61000-6-3/A1/ AC:2013
Schematics Network Connections
  Step Output Connections
  Digital I/O and Alarm Output Connections
  Step Output Connections

Power Factor Controller

RAPIDUS is a 3 phase Reactive Power Control Relay that capable of inductive and capacitive compensation. At the same time, with the energy measurements menu, it can perform detailed energy analysis. Dynamic capacitor monitoring allows continuous updating of step power values. Thanks to unique intelligent mode, it activates the step combination closest to the measured demand by calculating their lifetime.

CE Certificate
Ukrayna Uygunluk Sertifikası
Rapidus Software [exe]
RAPIDUS 1 Phase User Guide [pdf]
606011 Power Factor Controller (1Ø-12 steps)