Klemsan
600106 VT3-ACDC-24
True RMS Voltage Transducer

  • TECHNICAL INFO
  • CERTIFICATES
  • DOWNLOADS
  • ORDER INFO
  • CREATE PDF
General
  Casing Width (mm) 36
  Connections Screw terminal
Input Signal Configurable Voltage Range 0-24VAC
    0-36VAC ---
    0-54VAC
    0-80VAC ---
    0-120VAC
    0-170VAC ---
    0-250VAC
    0-400VAC ---
    0-450VAC
    0-500VAC ---
    0-24VDC
    0-54VDC
    0-120VDC
    0-250VDC
    0-450VDC
  Configurable Current Range 0-1AAC ---
    0-2AAC ---
    0-3AAC ---
    0-4AAC ---
    0-5AAC ---
Input Signal Frequency 40-70 Hz
  Surge Overload <2xU Input Max. Range (5 pulses 1sec.)
  Constant Overload Max. 600V
  Input Impedances 240 kΩ
Output Type 0-20mA
    4-20mA
    ±20mA
    20-0mA
    20-4mA
    0-5V
    0-10V
    ±5V
    ±10V
    10-0V
  Analog Output Max. Current 24 mA
    Max. Voltage 12V
    Max. Load 10 Ω (for voltage) / 600 Ω (for current)
Supply Voltage AC ---
    DC 10-36V
Supply Frequency ---
Power Consumption DC <1.5W
  AC <4VA
General Isolation 1.5 kVrms, 3-way
  Test Voltage between Input-Output 4 kV during 1 min.
  Linearity <0.2%
  Response Time 350ms
  Ripple <80mV
  Accuracy <0.2% (full scale, 25°C)
  Temperature Coefficient 150 ppm/°C
Ambient Conditions Operating Temperature -20°C +60°C
  Storing Temperature -40°C +75°C
  Relative Humidity (No Condensation) Maks. 95%
General Protection Class IP20
  Mounting Type Panel or Rail
EMC-EMI Radiated Emissionas Test, 61000-6-2/AC:2012, 61000-6-4:2007/A1:2011
General Packing Unit 1
  Dimensions
  Weight (g) 70

CE Certificate
General Product Information [pdf]
600106 True RMS Voltage Transducer