Ascon 311
SKU:
602300
Thermocouple Transducer
How can I find pricing information?
To access product pricing information, create an order list and contact us.
Min. order quantity : 1
Packing unit : 1 pcs.
-
Pick up from the Woodmart Store
To pick up today
Free
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
Free
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
Free
-
Warranty 1 year
-
Free 30-Day returns
Commercial Information
Product Sales Code
602300
Packing Unit
1 pcs.
Customs Tariff No.
854370900019
Weight per piece (inc. packing)
0.042 kg.
Product Description
Thermocouple Transducer
Technical Information
general
Connection Type
Screw terminal
Protection Class
IP20
Weight G
42
Packaging Quantity
1
Dimensions
--
Case Width Mm
17,5
Mounting Type
Rail Mounted
Isolation
3 way - 1,5 kV RMS
Measurement Error Full Scale
< 0.2% (Full Scale)
Response Time
< 150ms
Temperature Coefficient
= 0.004%/°C
Sensor Fault Indication
The situation of input signal is at least 10 % different than adjusted value
power-supply
Voltage
11-30V DC
environmental-conditions
Operating Temperature
--
Storage Temperature
-40°C +75°C
Relative Humidity Non Condensing
Max. 95%
emc-emi
Radiated Emission Test 61000 6 2ac
2012, 61000-6-4
output
Output Signal
0-5V(0 - 20mA), 5 - 0V(20 - 0mA ), 0 - 10V( 4 - 20mA ), 10 - 0V( 20 - 4mA), -5...5V(20...20mA)
Linear Output Range
---
Max Load
= 600 Ohm ( Current Input ), = 10K Ohm ( Voltage Output )
Ripple
---
input
Input Type
V , mV , mA
Input Signal
0..60mV 0..100mV 0..250mV 0..500mV 0..1V 0..2V 0..2,5V 0..5V 0..10V 0..20V -6..60mV -100..100mV -250..250mV -500..500mV -1..1V -2..2V -2,5..2,5V -5..5V -10..10V -20..20V 0..5mA 0..10mA 0..20mA -5..5mA -10..10mA -20..20mA 4..20mA 0..24mA 4..24mA 0..12mA
Certificates

CE

UKCA

ROHS
Accessories
general
Connection Type
Screw terminal
Protection Class
IP20
Weight G
42
Packaging Quantity
1
Dimensions
--
Case Width Mm
17,5
Mounting Type
Rail Mounted
Isolation
3 way - 1,5 kV RMS
Measurement Error Full Scale
< 0.2% (Full Scale)
Response Time
< 150ms
Temperature Coefficient
= 0.004%/°C
Sensor Fault Indication
The situation of input signal is at least 10 % different than adjusted value
power-supply
Voltage
11-30V DC
environmental-conditions
Operating Temperature
--
Storage Temperature
-40°C +75°C
Relative Humidity Non Condensing
Max. 95%
emc-emi
Radiated Emission Test 61000 6 2ac
2012, 61000-6-4
output
Output Signal
0-5V(0 - 20mA), 5 - 0V(20 - 0mA ), 0 - 10V( 4 - 20mA ), 10 - 0V( 20 - 4mA), -5...5V(20...20mA)
Linear Output Range
---
Max Load
= 600 Ohm ( Current Input ), = 10K Ohm ( Voltage Output )
Ripple
---
input
Input Type
V , mV , mA
Input Signal
0..60mV 0..100mV 0..250mV 0..500mV 0..1V 0..2V 0..2,5V 0..5V 0..10V 0..20V -6..60mV -100..100mV -250..250mV -500..500mV -1..1V -2..2V -2,5..2,5V -5..5V -10..10V -20..20V 0..5mA 0..10mA 0..20mA -5..5mA -10..10mA -20..20mA 4..20mA 0..24mA 4..24mA 0..12mA

CE

UKCA