General
Measuring system
1Ø
LCD Screen
✔
Language Support
Turkish, English
Password Protection
✔
Current Transformer Ratio
1 - 5.000
Voltage Transformer Ratio
1 - 999.9
Connection Type
L-L/L-N
Number of Measurements in a Period
512
LCD/Display Refresh Period
<0.5 sec.
Networks
TT, TN,
Signal Waveforms
Control Operations and Functions
Compensation Modes
Rapidus (Intelligent control mode)
✔
Manual
✔
Step Configurations
Manually Assigned
✔
Predefined
1-1-1-1, 1-2-2-2, 1-2-4-4
Power (kVAr)
0.00-1000 adjustable
Type
3Ø capacitor, 1Ø capacitor
Power Factor Settings
Target 1 cosØ
0.8 cap. to 0.8 ind. adjustable
Target 2 cosØ
0.8 cap. to 0.8 ind. adjustable
Control Operations and Functions
Dual cosØ Target
✔
4 Quadrant operation for generators
✔
Time Delays
Step Activation Time
1-600 sec. adjustable
Step Deactivation Time
1-600 sec. adjustable
Step Discharge Time
3-1000 sec. adjustable
Energy Measurement
Multi Sub-Tariffs (Peak, Day and Off-Peak)
1Ø Phase Energy Meters
3Ø Phase Energy Meters
4 Quadrant Reactive Energy Meters
Current Measurement Input
Measurement Range
10mA-6A AC
Overvoltage Category
300 V Cat III
Measurement Surge Voltage
Power Consumption
<0.2 VA
Intermittent Overload
100A for 1 sec.
Sampling Frequency between 45-65 Hz
25.6 kHz
Voltage Measurement Input
Overvoltage Category
300 V Cat III
Measured Range L-N
120...510V AC ±10%
Measured Range L-L
120...510V AC ±10%
Measured Frequency Range
45-65 Hz
Power Consumption
<0.2 VA
Sampling Frequency between 45-65 Hz
25.6 kHz
Power Quality Measurements
THD - Voltage in %
✔
THD - Current in %
✔
Measurement Accuracy
According to IEC 61557-12
Total Active Power
Class 0.5
Total Reactive Power
Class 1
Total Apparent Power
Class 0.5
Total Active Energy
Class 0.5
Total Reactive Energy
Class 2
Frequency
Class 0.1
Current
Class 0.5
Neutral Current
Class 0.5
Voltage
Class 0.2
Power Factor
Class 0.5
THDV, THDI
Class 1
According to IEC 62053-22
Total Active Energy
Class 0.5S
According to IEC 62053-23
Total Reactive Energy
Class 2
Input and Outputs
Compensation Relay Outputs
Number of outputs
12
Type
NO (SPST)
Max. Switching Current
2A
Max. Switching Voltage
250VAC
Max. Switching Power
1250VA
Mechanical Lifetime
≥ 10.0000000 operations
Electrical Lifetime Operations (for NO side)
5×104(5A@250VAC) 1×105(5A@30VDC)
Alarm Relay Outputs
Number of outputs
2
Type
NO (SPST)
Max. Switching Current
4A
Max. Switching Voltage
250 VAC
Max. Switching Power
1250 VA
Mechanical life time
≥ 10.0000000 operations
Electrical life time operations (for NO side)
5×104(5A@250VAC) 1×105(5A@30VDC)
Generator/ Day-Night Input
Number of Inputs
1
Frequency
45-65Hz
Input Present or Not
95-240VAC
Input and Outputs
Digital Outputs
---
Analog Outputs
---
Supply
Auxilary Supply Input
---
Voltage
La-Lb'den 120...510V AC ±10%
Frequency
45-65Hz
Supply
Consumption
AC
< 10VA
DC
---
Mechanical Properties
Weight (g)
Protection Class
Front IP40 / Rear IP20
Mounting Type
Panel Mount
Packing Unit
1
Cable Cross Sections
Voltage, Current, All Relay Outputs, Gen Input
Stranded:
2.5mm² - 14AWG
Ambient Conditions
Operating Temperature
-20°C +55°C
Storing Temperature
-30°C +80°C
Relative Humidity (no condensation)
Maks. 95%
EMC-EMI
EN 61000-6-1:2011
✔
EN 61000-6-3/A1/ AC:2013
✔
Schematics
Network Connections
✔
Step Output Connections
✔
Digital I/O and Alarm Output Connections
Step Output Connections
Power Factor Controller RAPIDUS 1 series is a monophase Reactive Power Control Relay. It has 4, 6, 8, 10 and 12-steps options and an optional RS485 port. The built-in temperature sensor measures the panel temperature and the fan output can be controlled by the relay outputs.
Ukrayna Uygunluk Sertifikası
RAPIDUS 1 Series User Manuel [pdf]
Download
606072
Power Factor Controller