General |
Password Protection |
✔ |
|
Current Transformer Ratio |
1 - 5000 |
Cable Cross Sections |
Supply , Voltage Current , Relay Outputs |
|
General |
Voltage Transformer Ratio |
1 - 5000 |
|
Demand Period |
1-60 min. adjustable |
|
Connection Type |
3F4T, 3F3T |
|
Measurements in Quadrants |
4 |
|
Number of Measurements in a Period |
256 |
|
Networks |
TT, TN, IT |
|
Min./Max./Demand Values |
✔ |
Energy Measurement |
Number of Tariffs |
1 |
|
1Ø Phase Energy Meters |
✔ |
|
3Ø Phase Energy Meters |
✔ |
Current Measurement Input |
Measurement Range |
10mA-6A AC |
|
Overvoltage Category |
300 V Cat II |
|
Measurement Surge Voltage |
2 kV |
|
Power Consumption |
<0.2 VA |
|
Intermittent Overload |
100 A for 1 sec. |
|
Sampling Frequency between 45-65 Hz |
12,8 kHz |
Voltage Measurement Input |
Overvoltage Category |
300 V Cat III |
|
Measured Range L-N |
1-300 Vrms |
|
Measured Range L-L |
2-500 Vrms |
|
Measured Frequency Range |
45-65 Hz |
|
Power Consumption |
<0.1 VA |
|
Sampling Frequency between 45-65 Hz |
12,8 kHz |
Power Quality Measurements |
Harmonics for Current and Voltage Phases |
Up to 31st |
|
THD - Voltage in % |
✔ |
|
THD - Current in % |
✔ |
Other Measurements |
Run Hour (Operating Time for Load in Hours) |
✔ |
|
On Hour (Operating Time for Meter in Hours) |
✔ |
|
Int Counter (Number of Power Interruptions) |
✔ |
Measurement Accuracy |
According to IEC 61557-12 |
Total Active Power |
Class 0.5 |
|
|
Total Reactive Power |
Class 1 |
|
|
Total Apparent Power |
Class 0.5 |
|
|
Total Active Energy |
Class 0.5 |
|
|
Total Reactive Energy |
Class 2 |
|
|
Frequency |
Class 0.1 |
|
|
Current |
Class 0.5 |
|
|
Neutral Current |
Class 0.5 |
|
|
Voltage |
Class 0.2 |
|
|
Power Factor |
Class 0.5 |
|
|
THDV, THDI |
Class 1 |
|
According to IEC 62053-22 |
Total Active Energy |
Class 0.5S |
|
According to IEC 62053-23 |
Total Reactive Energy |
Class 2 |
Inputs and Outputs |
Alarm Relay Outputs |
Type |
|
Supply |
Voltage |
AC |
85-300V |
|
|
DC |
85-300V |
|
Consumption |
AC |
<6VA |
|
|
DC |
<3W |
Supply |
Frequency |
45-65Hz |
Communication |
Protocol |
Modbus RTU |
|
Baud Rate |
1200-57600 bps adjustable |
|
Parity Number |
Odd, Even, None |
|
Stop Bit |
1 |
|
Address |
1-247 |
|
Isolation |
2750V RMS |
Mechanical Properties |
Weight (g) |
|
|
Protection Class |
IP20 |
|
Mounting Type |
Rail Mounted |
|
Packing Unit |
|
Cable Cross Sections |
Supply, Voltage, Current, Relay Outputs |
Stranded: |
2.5mm² - 14AWG |
|
|
Solid: |
4mm² - 12AWG, 2x1.5mm² - 2x16AWG |
|
Digital I/O, RS 485, Analog Output |
Stranded: |
1.5mm² - 16AWG |
|
|
Solid: |
1.5mm² - 16AWG, 2x0.75mm² - 2x18AWG |
Ambient Conditions |
Operating Temperature |
-20°C +70°C |
|
Storing Temperature |
-30°C +80°C |
|
Relative Humidity (No Condensation) |
Maks. 95% |
General |
|
|
|
Dimensions |
|